APC Smart-UPS RC 2000VA, 230V, LCD, 4x IEC 60320 C13 outlets
| Main |
Main Input Voltage | 230 V |
Other Input Voltage | 220 V 240 V |
Main Output Voltage | 230 V |
Other Output Voltage | 220 V 240 V |
Rated power in W | 1600 W |
Rated power in VA | 2000 VA |
Input Connection Type | IEC 60320 C14 |
output connection type | 4 IEC 60320 C13 |
Cable length | 1.22 m |
Number of cables | 1 |
battery type | Lead-acid battery |
Provided equipment | Basic UPS signalling RS-232 cable CD with software User manual USB cable |
| Batteries & Runtime |
Efficiency | |
Number of battery filled slots | 1 |
Number of battery free slots | 0 |
Battery recharge time | 3h |
Additional information | Configurable for 220 : 230 or 240 nominal output voltage |
battery voltage | 48 V |
Battery charger power | 144 W rated |
Battery power in VAH | 432 VAh runtime |
Battery life | 3…5 year(s) |
Extended runtime | 1 |
| Physical |
Colour | Charcoal |
Height | 26 cm |
Width | 14.5 cm |
Depth | 39.7 cm |
Net weight | 18 kg |
Mounting preference | No preference |
Mounting mode | Rack-mounted with kit |
Two post mountable | 0 |
USB compatible | Yes |
Mounting position | Vertical |
| Input |
Network frequency | 50/60 Hz |
Load power factor | 0.8 |
Input voltage limits | 160…275 V |
| Output |
Harmonic distortion | Less than 2 % |
Maximum configurable power in VA | 2000 VA |
Maximum configurable power in W | 1600 W |
Crest factor | 3 : 1 |
UPS type | Double conversion online |
bypass type | Built-in bypass |
Output harmonic distortion | < 3% linear load |
Wave type | Sine wave |
Output frequency | 50/60 Hz +/- 3 Hz sync to mains 50/60 Hz +/- 1 Hz unsynchronised |
| Communications & Management |
Emergency power off | Yes |
Free slots | 1 |
Alarm | Alarm when on battery : distinctive low battery alarm : configurable delays |
| Packing Units |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 23 cm |
Package 1 Width | 59 cm |
Package 1 Length | 32.5 cm |
Package 1 Weight | 19.8 kg |